Honeywell DLG976 mod.02 0366002 control box
Resideo DLG976 mod.02 0366002 control unit for 2-stage forced draught and combi oil/gas burners. Possible flame detectors: Ionisation probe Infrared flicker detector 1020 UV flame sensor UVD 971 Honeywell DLG976 mod.02 gas burner control technical data: Operating voltage: 220 / 240 V (-15... +10%) Air proving switch: 1 working contact 4 A, 230V Sensitivity (operation): 1 µA Min. required ion. current: 1.5 µA Sensitivity for stray light: 0.4 µA Cable length: < 3 m Weight incl. wiring base: 190 g Mounting position: any Protection class: IP 40 Approved ambient parameter for control and flame detector max. 95% at 30°C Build-up of ice, penetration of water and condensing water are inadmissible Approvals according to European standards EN 298 and EN 230, as well as all other relevant Directives and standards Classified acc. to EN 298 FTLLXN