Kromschroder 88600013 Control box BCU370WI2FEU0D3Z001
Kromschroeder 88600013 BCU370WI2FEU0D3Z001 gas burner safety control box controls, ignites and monitors industrial forced draught burners of unlimited capacity in intermittent or continuous operation. Kromschroder BCU370WI2FEU0D3Z001 88600013 gas burner safety control box technical data Mains voltage: 230 V AC, 50/60 Hz Flame control with UV sensor or ionisation sensor Flame signal for Ionization control: 1 – 28 μA, UV control: 1 – 35 μA For intermittent or continuous operation Air pressure check during pre-purge and operation by external air pressure switch DL Maximum length of ignition cable with integrated electronic ignition: 1 m Maximum length of ionisation/UV cable: 50 m (164 ft) Max. number of operating cycles: 250,000 Ambient temperature: -20 - +60 °C (-4 – +140 °F) Enclosure: IP 54 pursuant to IEC 529 Housing made of impact-resistant and heat-resistant plastic. Plug-in upper section with operating and display elements. Lower section with connection terminals, earthing strip and pre-wired neutral bus with spacious wiring chamber Weight: 1.8 kg Krom schroder BCU370WI2FEU0D3Z001 88600013 gas burner control unit application It can be used for directly ignited forced draught burners or forced draught burners ignited with pilot burner. Kromschroeder 88600013 BCU370WI2FEU0D3Z001 control box activates the fan and sets the connected butterfly valve to Pre-purge and Ignition position. After pre-purge and burner start, the Enable signal is issued to an external controller, which positions the butterfly valve in accordance with the output demand. Post-purge occurs after the end of burner operation. Kromschroder 88600013 BCU370WI2FEU0D3Z001 control unit monitors the gas and air pressure. An optionally integrated tightness control function checks the valves with an external gas pressure switch. Programmability by means of the optical interface and BCSoft PC software guarantees optimum adaptation to the relevant application. Adjustable start-up attempts and automatic restart, which can be activated, ensure the high flexibility of the burner equipment. The quick-start option allows standard-compliant startup of the forced draught burner without pre-purge after normal shutdown. This avoids unnecessary admission of air into the combustion chamber. The heat output is available as quickly as possible after a temperature demand.