Honeywell R7886A1001 self check UV amplifier 3.0/2.0s, C7076
Honeywell R7886A 1001 amplifiers have a self-monitoring function. Honeywell R7886 A 1001 amplifiers check the detectors and all electronic components of the flame detection system 12 times per minute. The relay modules of the 7800 and R7140 series perform a safety shutdown in case of a malfunction of the flame detection system. Honeywell R7886A1001 amplifier technical data The intensity of the flame signal is in the range from 0 to 5.0 V. They connected to the 7800 relay module via the edge connector of the printed circuit board, configured for its own orientation. Flame signal control sockets for measuring the voltage of the flame signal on the amplifier. Dimensions: width - 91 mm, height - 85mm, thickness - 23mm. Weight: 70 g Ambient temperature: -40 C to +60 C Accessories: 123514A Flame Rectifier simulator. 203659 is an ultraviolet flame simulator.