Electrode Ecoflam 65320868
Ionization electrode Ecoflam 126 mm, 65320868 Original flame sensor for safe operation of Ecoflam gas burners. The Ecoflam 65320868 ionization electrode is an original component of the safety system for Ecoflam gas burners. The product is designed for continuous monitoring of the presence of a flame in the combustion chamber and transmitting an ionization signal to the combustion control automation. If your burner starts but shuts down in emergency mode after a few seconds, the cause is often a malfunction of this element. Technical specifications: Parameter Value; Part numbers 65320868, BFE01039/3, 390.946.130; Manufacturer Ecoflam (Italy); Electrode type Ionization (flame control); Total length 126 mm; Rod diameter Ø3 mm; Rod length 49 mm; Ceramic insulation diameter Ø8 mm; Ceramic insulation length 60 mm; Connection type Plug Ø4 mm; Rod bend angle 60°. Key advantages: Original Ecoflam equipment: Full compliance with factory specifications guarantees compatibility and reliable operation as part of Ecoflam burners. Optimal length 126 mm: This electrode has a total length of 126 mm (ceramic part 60 mm, rod 49 mm with a 60° bend). This is the optimal size for installation in medium power burners, ensuring reliable contact with the stable combustion zone. Fast safety system response: The advantage of the ionization electrode is its very fast response when the flame disappears, preventing emergency situations and fuel leaks. Real-time flame monitoring: The ionization electrode continuously monitors the presence of a flame in the combustion chamber. In its absence, the automation instantly stops the fuel supply, ensuring safe operation of the equipment. High combustion efficiency: Stable operation of the ionization electrode