+370 661-08345Spedizione in UE
Tutti i prezzi IVA esclusaAssistenzaSegui la richiesta
KROM
Scatola di comando Siemens LFL1.622
Siemens

Scatola di comando Siemens LFL1.622

SKU 884.124.024Su richiesta
703,90 €IVA esclusa
Richiedi il prezzo
Spedizione in UE

Siemens LFL1.622 burner control unit is used for start-up and monitoring of multi-stage or modulating gas, oil or combination forced-draft burners of medium and high power with intermittent operation. Main characteristics: Supply voltage: 230 V. Pre-purge time: 65s. Safety time: 2s. Safety time or first safety time when operating with pilot burner: 2 s. Time to ignition: 4s. Time to ignition: 4 s. Interval between voltage application to terminals: 10s. Interval between start of TSA' and valve shutdown at terminal: 10s. Interval between voltage application to terminals: 10s. Post-purge time: 12s. Interval between start command and voltage application to terminal: 2s. Start-up sequence duration: 95s. Second safety time for burners with pilot burner: 2s. Additional information: 30850

Codici ed equivalenze

3
Article884.124.024
SKULFL1.622
RefLFL1.622, 884.124.024