Resideo DKG972 mod.32 0332032 gas burner control unit controls atmospheric gas burners and certified to European standards. The system stores fault information, accessible even after power loss. Satronic DKG972 mod.32 control unit ensures safety during low voltage by preventing a restart and protecting the system. Honeywell DKG972 mod.32 0332032 gas burner control box technical data: Operating voltage: 220/240 V Sensitivity: 1.0 µA Minimum required ionization current: 1.5 µA Sensitivity to outside light: 0.4 µA Cable length: < 3 m Weight including base: 190 g Installation position: any Protection class: IP 40 Permissible climatic conditions for the device and flame sensor humidity: max. 95% at 30°C Permissible operating temperature range: -20 °C ... +60°C Permissible storage temperature range: -20°C ... +80°C Ice formation, water exposure and condensation are not allowed Approved in accordance with European standards EN 298 and EN 230, as well as other relevant directives and standards Safety time: 50 seconds Time after ignition: 49 seconds Switching time to the second stage: 55 seconds