
Kromschroeder UVC1L1G1A (84320300) Sensore di fiamma UV
In industrial thermoprocessing systems, Kromschroder UVC1L1G1A 84320300 flame detector is designed to monitor flames which emit UV radiation. Kromschroder U84320300 VC1L1G1A UV-sensitive detector is suitable for intermittent or continuous operation in conjunction with Kromschroder burner control units BCU, PFU. Kromschroeder 84320300 UVC1L1G1A UV cell technical data Series 1 Quartz glass heat guard lens Rp 1/2 internal thread and cooling air connection M20 cable gland Supply voltage: 100 to 230 V AC, 50/60 Hz (terminals L and N) Length of cable between UV flame detector and burner control unit: min. 2 m, max. 100 m Distance between UV flame detector and flame: 300 to 400 mm UV tube: P578, spectral range: 190 to 270 nm, max. sensitivity: 210 nm ± 10 nm Min. DC signal: 1 μA Housing: aluminum Cable gland for cable diameters of 7 to 13 mm Clamping range of the connection terminals: 0.5 to 1.5 mm2 Weight: 1 kg Ambient temperature: -20 to +80°C (-4 to +176°F) Storage temperature: -20 to +80°C (-4 to +176°F) Enclosure: IP 65 Safety class: 1 Pollution degree: internal environment: 2, eternal environment: 4 Krom schroder UVC1L1G1A 84320300 UV sensor designed lifetime This information on the designed lifetime is based on using the product in accordance with these operating instructions. Once the designed lifetime has been reached, safety-relevant products must be replaced. Designed lifetime of the UVC 1 (based on date of manufacture): 10 years. Designed lifetime of the UV tube: approx. 10,000 operating hours (approx. 1 year). This procedure applies to heating systems. For thermoprocessing equipment, observe local regulations. Kromschroeder UVC1L1G1A 84320300 flame detector declaration of conformity Krom schroder UVC1L1G1A 84320300 UV cell complies with the essential requirements of the following Directives and Standards: Directives: 2009/142/EC GAD (valid until 20 April 2018) 2014/30/EU 2014/35/EU Regulation: (EU) 2016/426 GAR (valid from 21 April 2018) The relevant Krom schroder 84320300 UVC1L1G1A UV sensor corresponds to the tested type sample. The production is subject to the surveillance procedure pursuant to Directive 2009/142/EC Annex II paragraph 3 (valid until 20 April 2018) and to Regulation (EU) 2016/426 Annex III paragraph 3 (valid from 21 April 2018).