+370 661-08345Expédition dans l'UE
Tous les prix hors TVAAideSuivre ma demande
KROM
Boîtier de commande Siemens « LAL3.25 »
Siemens

Boîtier de commande Siemens « LAL3.25 »

SKU 884.124.133Sur demande
840,20 €HT
Demander un prix
Expédition dans l'UE

Siemens LAL3.25 burner control unit is used for start-up and control of multi-stage or modulating forced-draft liquid fuel burners of medium and high power with intermittent operation and air pressure monitoring via functional check of the air pressure switch during start-up and operation. Yellow flame monitoring is performed using a photoresistive sensor QRB1…, blue flame monitoring using a RAR… sensor with a selenium photocell. Main characteristics: Supply voltage: AC 230 V. Pre-purge time: 22.5 s. Safety time: 5 s. Time to ignition: 2.5 s. Time after ignition: 15 s. Interval between voltage application to terminals: 7.5 s. Interval between voltage switching at terminals: 7.5 s. Post-purge time: 15 s. Fan motor start delay: 2.5 s. Start-up sequence duration: 47 s.

Références et équivalences

3
Article884.124.133
SKULAL3.25
RefLAL3.25, 884.124.133