Siemens „LAL2.25“-Steuergerät
Siemens

Siemens „LAL2.25“-Steuergerät

SKU 884.124.005Auf Anfrage
695,80 €zzgl. MwSt.
Preis anfragen
Versand in die EU

Siemens LAL2.25 electromechanical burner control is used for starting and controlling multi-stage or modulating forced-draft oil burners of medium and high power with intermittent operation and air pressure monitoring via functional test of the air pressure relay during start-up and operation. Yellow flame monitoring is performed using a photoresistive sensor QRB1…, blue flame monitoring using a RAR... sensor with selenium photocell. Main characteristics: Supply voltage: AC 220 V. Pre-purge time: 22.5 s. Safety time: 5 s. Time to ignition: 2.5 s. Time after ignition (ignition transformer connected to terminal): 15 s. Interval between voltage application to terminals 18 and 19 (fuel valve): 7.5 s. Interval between voltage switching at terminals: 7.5 s. Post-purge time: 15 s. Fan motor start delay: 2.5 s. Start sequence duration: 47 s. Additional information: 31252

Nummern und Referenzen

3
Article884.124.005
SKULAL2.25
RefLAL2.25, 884.124.005