Brahma 13992323 GVC25*S3Z*L3X*SRD-Gasventil
Valves BRAHMA GVC25*S3Z*L3X*SRD 13992323 can be equipped with a bypass valve and/or a gas pressure sensor with a fixed or adjustable set value, as well as an input pressure regulator to adjust and maintain a constant gas pressure. The electrical connections between the components of the system are made using a printed circuit board placed in a plastic housing. The valve system is electrically connected to the control unit via a DIN plug, ensuring easy connection in various applications. The presence of voltage is indicated by an LED, useful during installation and maintenance operations. Technical Specifications - Intended for: gas burners - Maximum excess pressure: 350 mbar - Inlet connection: Rp 3/4" - Outlet connection: Rp 3/4" - Power supply: 230 V - Ambient temperature range: from -10 to +60 °C - Maximum opening time: 1 s - Maximum closing time: 1 s - Power: 83 W - Electromagnetic valves V1 and V2: Class A - Dust and moisture protection class: IP40 - Connection type: DIN plug - Dimensions: 18.3x21.8x19 cm Installation Adhere to relevant national and European standards (e.g., EN60335-1) regarding electrical safety. Assemble the gas solenoid valve BRAHMA GVC25*S3Z*L3X*SRD 13992323 for installation so that the arrow on the valve body points in the same direction as the fuel flow. When assembling the gas control block BRAHMA GVC25*S3Z*L3X*SRD 13992323 to the installation pipeline, avoid twisting the sheath; always use a hexagonal key on the valve body. Ensure that no foreign objects have entered the housing of the gas valve BRAHMA GVC25*S3Z*L3X*SRD 13992323. Ensure that the maximum fuel input pressure never exceeds the value indicated on the product label.